Emergency lighting is a legal requirement in most non-domestic premises and the shared areas of residential blocks in the UK. A fire risk assessment checks that it exists, works, covers every escape route and is tested and recorded under BS 5266-1. If it isn’t, the Responsible Person is liable.
Contents
- What is emergency lighting and why does it matter?
- What are the emergency lighting regulations in the UK?
- What are the emergency lighting requirements under BS 5266-1?
- What does a fire risk assessment check for emergency lighting?
- How often must emergency lighting be tested?
- Common emergency lighting failures
- Who is responsible for emergency lighting?
- What happens if emergency lighting is not compliant?
- Get your emergency lighting checked
- Frequently asked questions
What is emergency lighting and why does it matter?
Emergency lighting is a battery-backed or centrally powered lighting system that switches on automatically when the normal mains supply fails, so people can find their way out of a building safely. In a fire, smoke and power loss can make a familiar corridor impossible to navigate within seconds. Emergency lighting keeps exits, stairs and escape routes visible long enough for everyone to leave.
There are two main types of emergency lighting:
- Escape route lighting: lights corridors, stairs, exits and changes of direction so people can leave.
- Standby lighting: lets normal activity continue during a power cut. It is not usually a legal requirement, but some businesses choose to install it.
This guide covers the first type, because that is what the law and a fire risk assessment focus on.
What are the emergency lighting regulations in the UK?
The emergency lighting regulations in England and Wales come from the Regulatory Reform (Fire Safety) Order 2005, supported by the British Standard BS 5266-1. The Order requires the Responsible Person to carry out a fire risk assessment. Where that assessment shows emergency lighting is needed, it must be provided and kept in working order. BS 5266-1:2016 is the code of practice that explains how to design, install, test and maintain it.
| Regulation or standard | What it covers |
|---|---|
| Regulatory Reform (Fire Safety) Order 2005 | Legal duty to assess fire risk and provide adequate escape lighting (England and Wales) |
| BS 5266-1:2016 | Code of practice for emergency lighting of premises: design, installation, testing and maintenance |
| BS EN 1838 | Minimum light levels and performance for emergency escape lighting |
| BS EN 50172 / BS 5266-8 | Inspection, testing and record-keeping for emergency escape lighting systems |
| Fire (Scotland) Act 2005 and Fire and Rescue Services (Northern Ireland) Order 2006 | Equivalent duties in Scotland and Northern Ireland |
The Order applies to non-domestic premises and to the common parts of multi-occupied residential buildings, including HMOs, blocks of flats, care homes, offices, shops and warehouses.
What are the emergency lighting requirements under BS 5266-1?
The emergency lighting requirements in BS 5266-1 cover where lights must be placed, how bright they must be and how long they must last. The standard expects the system to be designed around your building’s layout, occupancy and escape routes, not fitted to a generic template.
Where emergency lighting is needed
Emergency lighting should be provided along the full escape route, including:
- Exit doors and exit signs
- Corridors, stairways and landings, with a light at each flight of stairs
- Changes of direction and intersections of corridors
- Fire alarm call points and firefighting equipment
- First aid points
- Lifts, larger toilets and windowless rooms
- Open areas above 60 m² and high-risk task areas
Light levels and duration
Under BS EN 1838, escape routes generally need at least 1 lux along the centre line and open areas need at least 0.5 lux. High-risk task areas need 10% of the normal lighting level, with a minimum of 15 lux. Lights must reach 50% of their required output within 5 seconds of a power failure and full output within 60 seconds.
Most systems are designed to run for 3 hours after a power failure. A shorter rated duration may be acceptable in some premises, but only where the fire risk assessment supports it, so confirm the duration for your building with a competent assessor.
Maintained and non-maintained lighting
| Type | How it works | Typical use |
|---|---|---|
| Maintained | The light is on all the time and stays on when the mains fails | Exit signs, cinemas, bars, public spaces |
| Non-maintained | The light is off until the mains fails | Corridors, offices, stairwells |
| Sustained | Has two lamps, one for normal use and one for emergencies | Mixed-use areas |
What does a fire risk assessment check for emergency lighting?
A fire risk assessment checks whether the emergency lighting in a building is suitable, in the right places, working and properly maintained. It looks at the system as part of the whole escape strategy. The assessor will usually check:
- Coverage: Is every escape route, exit, stair and change of direction lit?
- Signage: Are exit signs illuminated and visible from where people stand?
- Condition: Are luminaires clean, undamaged and not blocked by stored items or décor?
- Operation: Do the lights come on when the supply is cut?
- Records: Is there a logbook showing monthly and annual tests, with faults recorded and fixed?
- Changes to the building: Has a refit, partition or change of use made the original layout out of date?
- Certification: Is there a design, installation or periodic inspection certificate to BS 5266-1?
A fire risk assessment gives an overall view of the system, but it is not a replacement for a full emergency lighting test. If the assessor spots problems, they will recommend a specialist inspection and test. Our fire risk assessment service covers the emergency lighting checks and our dedicated emergency lights installation and testing service covers repairs, certification and ongoing testing.
How often must emergency lighting be tested?
Emergency lighting must be tested monthly with a short functional test and once a year with a full rated-duration test and every test must be recorded in a logbook. These intervals come from BS EN 50172 and BS 5266-8.
| Test | Frequency | What it involves |
|---|---|---|
| Short functional test | Monthly | Briefly simulate a power failure and check every light comes on and every charge indicator is working |
| Full duration test | Annually | Run lights on battery for their full rated time (usually 3 hours) to confirm they last |
| Visual inspection | Ongoing and at each test | Check for damage, dirt, blocked fittings and faulty signs |
A full duration test drains the batteries, so it should be scheduled when the building is unoccupied or when the lights can recharge, which takes around 24 hours. Any failed light should be repaired or replaced and the fix recorded.
If you are a landlord or managing agent, keep the same logbook alongside your other fire safety records, such as fire door inspections, smoke alarm testing and fire extinguisher servicing.
Common emergency lighting failures
The most common emergency lighting failures are flat batteries, missing test records and gaps in coverage after the building has changed. These are the problems assessors find most often:
- Batteries that no longer hold charge, usually after 3 to 4 years
- No logbook, or a logbook with gaps in the testing
- Exit signs that are not lit or are hidden behind stock or decorations
- Luminaires painted over, covered or blocked
- New walls, partitions or room changes with no matching lighting
- Lights switched off at the isolator or fed from the wrong circuit
- No test certificate for the original installation
Most of these are quick and inexpensive to fix once found. They become costly only when they are discovered after an incident or an enforcement visit.
Who is responsible for emergency lighting?
The Responsible Person is legally responsible for emergency lighting. Under the Fire Safety Order, this is the employer, building owner, landlord or managing agent who has control of the premises. In a multi-occupied building, responsibility for shared areas usually sits with the landlord or managing agent, while each tenant is responsible for their own space.
The Responsible Person can appoint a competent contractor to do the work, but the legal duty stays with them. Always check that the engineer or assessor is properly qualified and issues a certificate and written report. Our assessors hold MIFSM and TFRAR Tier-2 qualifications and provide full digital reporting.
What happens if emergency lighting is not compliant?
If emergency lighting is not compliant, the Responsible Person can face enforcement notices, prosecution and unlimited fines and in serious cases up to two years in prison. Fire and rescue authorities can also issue prohibition notices that restrict or stop the use of a building. Non-compliance can also affect insurance cover and increase liability if someone is hurt in a fire.
The cost of a regular inspection is small compared with these risks. Keeping tests up to date and records tidy is the simplest way to show you have met your legal duty.
Get your emergency lighting checked
Not sure whether your emergency lighting would pass a fire risk assessment? Property Checks provides emergency lighting installation, testing and certification, plus full fire risk assessments for landlords, businesses, HMOs, care homes and commercial buildings across London and the Home Counties.
- Same-day appointments available
- Qualified assessors with full digital reporting
- Transparent pricing with no hidden fees
Get a Quote Now or call us on 0208 432 9484 (Mon–Fri, 8am–6pm).
You can also explore our full range of fire safety services or read more answers on our FAQ page.
Frequently asked questions
Is emergency lighting a legal requirement in the UK?
Yes. Under the Regulatory Reform (Fire Safety) Order 2005, the Responsible Person must provide adequate emergency lighting wherever the fire risk assessment shows it is needed. This applies to most non-domestic premises and the shared areas of multi-occupied residential buildings.
Do HMOs and blocks of flats need emergency lighting?
Often, yes. Where escape routes such as shared corridors and stairwells are internal, windowless or used in the dark, the fire risk assessment will usually call for emergency lighting. The exact requirement depends on the building’s layout and risk.
What British Standard covers emergency lighting?
BS 5266-1:2016 is the main code of practice. It works alongside BS EN 1838 for light levels and BS EN 50172 (BS 5266-8) for testing and maintenance.
How long should emergency lighting last?
Most systems are designed to last 3 hours. A shorter duration may be acceptable in some buildings if the fire risk assessment supports it.
How often should emergency lighting be tested?
Test it monthly with a short functional test and annually with a full duration test and record every test in a logbook.
Does a fire risk assessment include emergency lighting?
Yes. The assessor checks coverage, condition, signage and test records. They may recommend a full specialist emergency lighting inspection and certificate if they find issues.
Can I test emergency lighting myself?
A competent person can carry out routine monthly functional tests and record them. The annual full duration test and any certification should be done by a qualified engineer.
How much does emergency lighting testing cost?
Cost depends on the size of the building and the number of fittings. Contact Property Checks for a quote.